For diverse applications


  • Nominal sizes 200 × 100 to 1500 × 800 mm, in increments of 1 mm
  • Low differential pressure and sound power level
  • Optional stainless steel casing or powder-coated casing for increased corrosion protection
  • Integration into the central BMS with TROXNETCOM
  • Universal installation options


Optional equipment and accessories

  • Electric actuator 24 V/230 V
  • Release temperature 72/95 °C

 

Useful additions

  • Duct smoke detectors

Application

Application

  • Fire dampers with CE marking and declaration of performance, for the isolation of duct penetrations between two fire compartments in the event of a fire
  • To prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments


Special characteristics

  • Declaration of performance in accordance with European Construction Products Regulation
  • Classification according to EN 13501-3, to EI 120
    (ve, ho, i ↔ o) S
  • Complies with the requirements of EN 15650
  • Tested for fire resistance properties in accordance with EN 1366-2 (300 Pa and 500 Pa negative pressure)
  • Certified mortar-based installation with reduced distances of 40 mm to supporting components or 60 mm between two fire dampers (flange to flange)
  • Perimeter gap may be up to 225 mm for mortar-based installation
  • 2 inspection accesses with bayonet fixing for single-handed operation
  • Meets the hygiene requirements of VDI 6022-1, VDI 3803-1, DIN 1946-4, EN 13779, of Ö-Norm H 6020 and H 6021, and of SWKI
  • Corrosion protection according to EN 15650 in connection with EN 60068-2-52
  • Closed blade air leakage to EN 1751, class 2
  • Casing air leakage to EN 1751, class C (B + H ≤700, class B)
  • Low differential pressure and sound power level
  • Any airflow direction
  • Integration into the central building management system with the international standard fire damper system in accordance with IEC 62026-2 with AS interface is possible


Classification

  • Leistungsklasse bis EI 120 (ve , ho , i ↔ o) S nach EN 13501-3


Nominal sizes

  • B × H: 200 × 100 – 1500 × 800 mm (intermediate sizes in increments of 1 mm)
  • L: 305 mm or 500 mm


Variants

  • With fusible link
  • With spring return actuator
  • With spring return actuator and duct smoke detector


Parts and characteristics

  • Release temperature 72 °C or 95 °C (for use in warm air ventilation systems)
  • Single-handed operation


Attachments

  • Limit switch for damper blade position indication
  • Spring return actuator for 24 V AC/DC or 230 V AC supply voltage
  • Network module for the integration with AS-i or LON networks
  • Spring return actuator and wired duct smoke detector, 24 V DC or 230 V supply voltage
  • All attachments can be retrofitted


Accessories

  • Installation kit ES for dry mortarless installation in lightweight partition walls or compartment walls with metal support structure and cladding on both ends
  • Installation kit ES for dry mortarless installation into timber stud walls / half-timbered constructions and solid wood walls
  • Installation kit ES for dry mortarless installation into shaft walls with or without metal support structure but with cladding on one side
  • Installation kit WE for dry mortarless installation remote from solid walls, remote from solid ceiling slabs, and remote from lightweight partition walls with metal support structure and cladding on both sides
  • Installation kit WA for dry mortarless installation on the face of solid walls and ceiling slabs
  • Installation kit ES for dry mortarless installation in wooden beam ceilings and solid wood ceilings
  • Flexible connectors
  • Cover grille
  • Circular spigots
  • Profile connecting frame


Useful additions

  • Duct smoke detector RM-O-3-D
  • Duct smoke detector with airflow monitor RM-O-VS-D


Construction features

  • Rectangular or square construction, rigid casing, both flanges with fixing holes
  • Suitable for the connection of ducts, cover grilles, spigots, flexible connectors or profile connecting frames
  • The release mechanism is accessible and can be tested from the outside
  • 2 inspection access panels, Ø110 mm, which can be opened without any tools
  • Remote control with spring return actuator


Materials and surfaces

Casing:

  • Galvanised sheet steel
  • Galvanised sheet steel, powder-coated RAL 7001
  • Stainless steel 1.4301


Damper blade:



  • Special insulation material
  • Special insulation material with coating


Other components:



  • Damper blade shafts and drive linkage made of galvanised steel, in constructions -1 and -2 made of stainless steel
  • Plastic bearings
  • EPDM and TPE seals


The construction variants with stainless steel or powder-coated casing meet even more critical requirements for corrosion protection. Detailed listing on request.


Standards and guidelines

  • Construction Products Regulation
  • EN 15650 Ventilation for buildings – Fire dampers
  • EN 1366-2 Fire resistance tests for service installations – Fire dampers
  • EN 13501 Fire classification of construction products and building elements
  • EN 1751 Ventilation for buildings – Air terminal devices


Supply package

If attachments and accessories are factory set with the fire dampers, they are already included in the order code. Installation situations may require supplementary materials for assembly and fixing, such as mortar, screws, mineral wool, etc., to ensure correct installation. Such materials are not included in the scope of delivery, unless they are expressly described as part of the delivery. The selection of supplementary attachments or accessories as well as the determination and provision of materials for assembly and fixing is the responsibility of the parties involved in the construction
and must be carried out taking into account the desired classification.


Maintenance

  • The functional reliability of the fire damper must be tested at least every six months; this has to be arranged by the owner of the ventilation system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306 and DIN 31051. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later. If 2 consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later
  • A functional test involves closing the damper blade and opening it again; with a spring return actuator this can be done via remote control
  • Fire dampers must be included in the regular cleaning schedule for the ventilation system
  • For details on functional tests, maintenance and inspection refer to the installation and operating manual


Technical data

  • Nominal sizes: 200 × 100 to 1500 × 800 mm
  • Casing lengths: 305 and 500 mm
  • Volume flow rate range: up to 14400 l/s / up to 51840 m³/h
  • Differential pressure: up to 2000 Pa
  • Temperature range: -20 – 50 °C
  • Upstream velocity*: ≤ 8 m/s with standard construction; ≤ 12 m/s with spring return actuator


* Data applies to uniform upstream and downstream conditions for the fire damper




Incorrect use:

  • In Ex-areas
  • as a smoke control damper
  • outdoors without sufficient protection against the effects of weather
  • in atmospheres where chemical reactions, whether planned or unplanned, may cause damage to the fire damper or lead to corrosion

Teknik bilgiler

Function, Technical Data, Quick Sizing, Specification Text, Order Code

  • FUNCTION
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE

 

 


Nominal sizes200 × 100 – 1500 × 800 mm ⁴
Casing lengths305 and 500 mm
Volume flow rate rangeup to 14400 l/s or 51840 m³/h
Differential pressure rangeUp to 2000 Pa

Temperature range 1, 3

-20 to 50 °C
Release temperature72 °C or 95 °C (for warm air ventilation systems)
Upstream velocity ²

Standardausführung ≤ 8 m/s,
Ausführung mit Federrücklaufantrieb ≤ 12 m/s


¹ Temperatures may differ for units with attachments. Details for other applications are available on request.
² Data applies to uniform upstream and downstream conditions for the fire damper.
³ Condensation and the intake of humid fresh air have to be avoided as otherwise operation will be impaired or not be possible.
⁴ Damper blade with lip seal for sizes 1 and 2, damper blade with travel stop seal for size 3.

Sizes see functional description

 
Free area and resistance coefficient, width 200 – 800 mm

H [mm]B [mm]
200250300350400450500550600650700750800
100A [m²]0.0130,0160.0200,0230.0270,0300.0340,0370.0410,0440.0480.0510.055
100ζ1.050,960.880,830.780,750.710,690.660,640.620.610.59
125A [m²]0.01750,02220.0270,03170.03650,04120.0460,05070.05550,06020.0650.06970.0745
125ζ0.930,850.780,730.690,660.630,610.590,570.550.540.52
150A [m²]0.02210,02810.03410,04010.04610,05210.05810,06410.07010,07610.08210.08810.0941
150ζ0.850,770.710,670.630,600.580,550.540,520.500.490.48
160A [m²]0.0240,0300.0370,0430.050,0560.0630,0690.0760,0820.0890.0950.102
160ζ0.660,600.550,520.490,470.450,430.410,400.390.380.37
200A [m²]0.0310,0400.0480,0570.0650,0740.0820,0910.0990,1080.1160.1250.133
200ζ0.740,670.620,580.550,520.500,480.470,450.440.430.41
250A [m²]0.03970,05070.06170,07270.08370,09470.10570,11670.12770,13870.14970.16070.1717
250ζ0.670,610.560,530.500,470.450,440.420,410.400.380.37
300A [m²]0.04890,06240.07590,08940.10290,11640.12990,14340.15690,17040.18390.19740.2109
300ζ0.620,560.520,490.460,440.420,400.390,380.360.350.34
350A [m²]0.05810,07410.09010,10610.12210,13810.15410,17010.18610,20210.21810.23410.2501
350ζ0.580,520.480,450.430,410.390,380.360,350.340.330.32
400A [m²]0.06730,08580.10430,12280.14130,15980.17830,19680.21530,23380.25230.27080.2893
400ζ0.540,490.460,430.400,390.370,350.340,330.320.310.30
450A [m²]0.07650,09750.11850,13950.16050,18150.20250,22350.24450,23550.25480.27410.2934
450ζ0.570,510.470,430.410,390.370,350.340,330.320.310.30
500A [m²]0.08570,10920.13270,15620.17970,20320.22670,25020.27370,2660.28780.30960.3314
500ζ0.540,480.440,410.390,370.350,340.330,310.300.300.29
550A [m²]0.12640,15070.1750,19930.22360,24790.27220,29650.32080.34510.3694
550ζ0.420,400.370,350.340,320.310,300.290.280.28
600A [m²]0.13940,16620.1930,21980.24660,27340.30020,3270.35380.38060.4074
600ζ0.410,380.360,340.320,310.300,290.280.270.27
650A [m²]0.15240,18170.2110,24030.26960,29890.32820,35750.38680.41610.4454
650ζ0.390,370.350,330.310,300.290,280.270.260.26
700A [m²]0.16540,19720.2290,26080.29260,32440.35620,3880.41980.45160.4834
700ζ0.380,350.330,320.300,290.280,270.260.250.25
750A [m²]0.17840,21270.2470,28130.31560,34990.38420,41850.45280.48710.5214
750ζ0.370,340.320,310.290,280.270,260.250.250.24
800A [m²]0.19140,22820.2650,30180.33860,37540.41220,4490.48580.52260.5594
800ζ0.360,330.320,300.290,270.260,260.250.240.23

① Parameter 


Free area and resistance coefficient, width 850 – 1500 mm

H [mm]B [mm]
900100011001200130014001500
200A[m²]0.1170.16650.14420.15780.17140.1850.1986
200ζ0.440.420.400.390.380.360.35
250A[m²]0.160.21570.19720.21580.23440.2530.2716
250ζ0.390.370.350.340.330.320.31
300A[m²]0.2030.26490.25020.27380.29740.3210.3446
300ζ0.350.340.320.310.300.290.28
350A[m²]0.2460.27460.30320.33180.36040.3890.4176
350ζ0.320.310.300.290.280.270.26
400A[m²]0.2890.32260.35620.38980.42340.4570.4906
400ζ0.300.290.280.270.260.250.25
450A[m²]0.3320.37060.40920.44780.48640.5250.5636
450ζ0.290.280.260.260.250.240.23
500A[m²]0.3750.41860.46220.50580.54940.5930.6366
500ζ0.270.260.250.240.240.230.22
550A[m²]0.4180.46660.51520.56380.61240.6610.7096
550ζ0.260.250.240.230.230.220.21
600A[m²]0.4610.51460.56820.62180.67540.7290.7826
600ζ0.250.240.230.220.220.210.20
650A[m²]0.5040.56260.62120.67980.73840.7970.8556
650ζ0.240.230.220.220.210.200.20
700A[m²]0.5470.61060.67420.73780.80140.8650.9286
700ζ0.240.230.220.210.200.200.19
750A[m²]0.590.65860.72720.79580.86440.9331.0016
750ζ0.230.220.210.200.200.190.19
800A[m²]0.6330.70660.78020.85380.92741.011.0746
800ζ0.220.210.200.200.190.190.18

① Parameter 



Quick sizing tables provide a good overview of the volume flow rates with different sound power levels as well as of differential pressures of up to 35 Pa. Approximate intermediate values can be interpolated. Precise intermediate values can be calculated with our Easy Product Finder design program.


Volume flow rate qv for differential pressure Δpst < 35 Pa
200 – 650 mm

H [mm]LWA [dB(A)]B [mm]
200250300350400450500550600650
10035390484577668759849938102711161205
1253550762774586297810931208132214351548
150356197649071048118813261464160117371873
1603572889710631227139015501710186920272185
20035835102812161402158617691950213023092487
250351026126414961725195121742396261628353053
300351232151217862056232125842844310333603615
350351434175720712379268329843281357738704161
400351634199723512698303933773710404143694696
450351474185622252585293832863629396943054640
500351647207124802878326936524031440647785146
5503527333169359540154429483852435645
6003529833456391943744823526657046139
6503532323742424147305213568961606627
7003534794026456050845600610966137112
7503537254308487754355984652670627592
8003539704589519357846367694175088070


Volume flow rate qv for differential pressure Δpst < 35 Pa
700 – 1500 mm

H [mm]LWA [dB(A)]B [mm]
700750800900100011001200130014001500
10035129313801468
12535166017721883
15035200821422276
16035234124972653
200352664284130172633291531963476375440314308
250353270348637013422378541474506486452215576
300353869412243744172461150485482591563456774
350354451473950274895540659146419692274237922
400355020534356645597617767537327789784659031
4503549725302563062826929757282118847948010110
50035551258756237695576678374907797761047111164
550356044644068347616839291629926106871144412198
6003565706998742482699107993810763115841240113214
65035709175518008891498131070411589124691334414216
700357606809885859553105111146112405133431427615204
7503581188640915810186112031221113213142081519716181
8003586269178972710813118891295514013150641610917149


Volume flow rate qv for differential pressure Δpst < 35 Pa
200 – 650 mm

H [mm]LWA [dB(A)]B [mm]
200250300350400450500550600650
10045525690841975110712391369149916291758
1254571087010881258142715951762192820942258
15045880111513231529173319352136233625342732
160451063130915521791202822622496272729583188
200451219149917752046231425802845310733683628
250451498184421832517284631733496381841374455
300451797220726072999338737704150452749025274
350452092256330223472391543544788521856466071
400452384291534313937443549275413589663756851
450452151270932473772428747945295579062826769
500452404302236194200476953295882642969717508
5504539874623524658586462705976508237
6004543535043571863827036768383228957
6504547155460618769027605830089889669
70045507658746653741881708913964810376
750455435628671167930873195221030311077
8004557926695757684409289101271095411774


Volume flow rate qv for differential pressure Δpst < 35 Pa
700 – 1500 mm

H [mm]LWA [dB(A)]B [mm]
700750800900100011001200130014001500
10045188620142142
12545242225852748
15045292931263322
16045341636443871
200453887414544023842425446635071547758826285
250454771508654004993552360506575709776178136
300455645601463826088672873657999863092589884
350456494691573347142788886299366101001083011558
4004573247795826481669012985310690115221235113177
450457254773582149166101101104811980129081383114751
5004580428572910010147111861221713243142631527816289
5504588189397997111113122441336714483155931669717797
600459586102111083212065132871449915704169021809319280
6504510345110161168313006143171561716908181921947020741
7004511098118141252613938153361672218099194672082822183
7504511844126061336214861163451781619277207292217223609
8004512586133911419115777173461890120444219782350325020

Fire damper in line with the European product standard DIN EN 15650 in square or rectangle construction style with 2 large inspection accesses that can be operated without tools. Tested for fire resistance properties according to DIN EN 1366-2 (300 Pa and 500 Pa negative pressure), with CE label.

The fire damper manufacturer's declaration of performance (DoP) provides proof that a product is suitable for the respective installation conditions, e.g. in, on the face of and remote from walls or ceilings, with the stated essential characteristics such as size, supporting construction, construction and installation type, and that it has the corresponding class of performance to EN 13501-3.
The ready-for-operation unit includes a release mechanism and a replaceable, fire-resistant damper blade, which, depending on the application, can be either horizontal or vertical. Depending on application, classified from: 
EI 30 (ve, ho i ↔ o) S to EI 120 (ve, ho i ↔ o) S



Suitable for:

Mortar-based installation

  • In solid walls, walls made from gypsum wall boards, lightweight partition walls, compartment walls, safety partition walls and walls to provide radiation protection
  • In shaft walls with metal support structures or steel support structures
  • In timber stud walls and timber frame walls, as well as solid wood and cross laminated timber walls
  • In und auf Massivdecken und in Kombination mit Holzbalken- und Vollholzdecken
  • In Vollholz- und Holzbalkendecken
  • Mehrfachbelegung bis 4,8 m² Brandschutzklappenfläche in massive Wände und Decken und Leichtbauwände
  • Can be installed together with FKRS-EU and FKR-EU in solid walls and ceiling slabs, lightweight partition walls and shaft walls
  • In lightweight partition walls, compartment walls, safety partition walls and radiation protection walls with metal support structures or steel support structures


Dry mortarless installation

  • In Leichtbauwände sowie Brandwände mit Metallständer und beidseitiger Beplankung
  • In timber stud walls and timber frame walls, as well as solid wood and cross laminated timber walls

 

  • In shaft walls with metal support structure or steel support structure, and in shaft walls without metal support structure
  • In solid wood and wooden beam ceilings
  • With an installation kit on the face of and remote from solid walls and ceiling slabs
  • Remote from lightweight partition walls (wall penetration)


Fire batt installation

  • In solid walls and ceiling slabs
  • In lightweight partition walls, compartment walls, safety partition walls and walls to provide radiation protection, with metal support structure or steel support structure
  • In timber stud walls, half-timbered constructions, solid wood walls and CLT walls


Sizes from (B x H) 200 mm x 100 mm to 1500 mm x 800 mm, intermediate sizes in increments of 1 mm.
Optimised low-leakage casing, up to leakage class C to EN 1751 with low differential pressure and low sound power level.
Fire damper casing made of galvanised sheet steel, optionally galvanised sheet steel with powder coating RAL 7001 or stainless steel 1.4301.
Damper blade made of special insulation material; coating as an option
Corrosion protection according to EN 15650 in connection with EN 60068-2-52. Meets the hygiene requirements of VDI 6022-1, VDI 3803-1, DIN 1946-4, EN 13779, of Ö-Norm H 6020 and H 6021, and of SWKI Casing length 305 mm or 500 mm with a 30 mm (L = 500 mm) flange for the connection to ducts made of non-combustible or combustible materials. Thermal release at 72 °C or 95 °C (warm air ventilation systems) with a fusible link or thermoelectrically with a spring return actuator, push button and indicator light (LED). Constructions with a brushless actuator for opening and closing the fire damper, also when the ventilation system is running and independent of the nominal size, are particularly suitable for functional checks and for shutting off sections of the duct system. Retrofit of spring return actuators without modification of the rod is possible from the outside.


Special characteristics

  • Declaration of performance in accordance with European Construction Products Regulation
  • Classification according to EN 13501-3, to EI 120
    (ve, ho, i ↔ o) S
  • Complies with the requirements of EN 15650
  • Tested for fire resistance properties in accordance with EN 1366-2 (300 Pa and 500 Pa negative pressure)
  • Certified mortar-based installation with reduced distances of 40 mm to supporting components or 60 mm between two fire dampers (flange to flange)
  • Perimeter gap may be up to 225 mm for mortar-based installation
  • 2 inspection accesses with bayonet fixing for single-handed operation
  • Meets the hygiene requirements of VDI 6022-1, VDI 3803-1, DIN 1946-4, EN 13779, of Ö-Norm H 6020 and H 6021, and of SWKI
  • Corrosion protection according to EN 15650 in connection with EN 60068-2-52
  • Closed blade air leakage to EN 1751, class 2
  • Casing air leakage to EN 1751, class C (B + H ≤700, class B)
  • Low differential pressure and sound power level
  • Any airflow direction
  • Integration into the central building management system with the international standard fire damper system in accordance with IEC 62026-2 with AS interface is possible


Materials and surfaces

Casing:

  • Galvanised sheet steel
  • Galvanised sheet steel, powder-coated RAL 7001
  • Stainless steel 1.4301


Damper blade:



  • Special insulation material
  • Special insulation material with coating


Other components:



  • Damper blade shafts and drive linkage made of galvanised steel, in constructions -1 and -2 made of stainless steel
  • Plastic bearings
  • EPDM and TPE seals


Technical data

  • Nominal sizes: 200 × 100 to 1500 × 800 mm
  • Casing lengths: 305 and 500 mm
  • Volume flow rate range: up to 14400 l/s / up to 51840 m³/h
  • Differential pressure: up to 2000 Pa
  • Temperature range: -20 – 50 °C
  • Upstream velocity: ≤ 8 m/s with standard construction; ≤ 12 m/s with spring return actuator


Equivalence criteria

  • The declaration of performance according to the Construction Products Regulation describes all CE-certified installation types including the performance class up to EI 120 S according to EN 13501-3 as well as the essential characteristics of at least the


  • Hygienic requirements are fulfilled in accordance with VDI 6022-1, VDI 3803-1, DIN 1946-4, DIN EN 13779 as well as the Önorm H 6020 and H 6021 and the SWKI.


  • CE-marked and thus tested for fire protection according to EU regulation 305/2011 and evaluated according to machinery directive 2006/42/EC
  • CE-certified mortar-based installation at a distance ≥ 60mm between 2 fire dampers (flange to flange)
  • Combined mortar-based installation with circular fire dampers in solid walls, lightweight partition walls clad on both sides and shaft walls with metal stud system with cladding on one side
  • 2 inspection access panels Ø110 mm, with bayonet fixing (can be opened without tools)


  • Pressure loss < 15 Pa at reference size 400 × 200 mm and 6 m/s face velocity


  • Sound power < 38 dB (A) at reference size 400 × 200 mm and 6 m/s face velocity



Order code FKA2-EU
FKA2-EU1 – 7 / PL / 600 × 400 × 500 / ES / A0 / Z43
|||||||
1234567

1 TypeFKA2-EU Fire damper 2 ConstructionNo entry: standard constructionpowder-coated casing, RAL 70012 Stainless steel casing7 coated damper blade1 – 7 powder-coated casing, RAL 7001, and coated damper blade2 – 7 Stainless steel casing and coated damper bladeW2) with fusible link 95 °C (only for warm air ventilation systems)B3) with coated fusible link 72 °CWB3) with coated fusible link 95 °C (only for warm air ventilation systems) 3 Country of destinationupon request 4 Nominal size [mm]B × H × L 5 Accessories 1No entry: noneES1)WA1)WE1) 6 Accessories 2No entry: none0A – FR 7 AttachmentsZ00 – ZA14 1) Only for FKA2-EU with L = 500 mm2) Not combinable with Z...RM and ZA123) Only for attachment Z00 - Z03

FKA2-EU-W/PL/600×200×500/ES/A0/Z43 
Construction variantCasing (galvanised)
Release temperature95 °C
Country of destinationGermany
Nominal size600 × 200 × 500 mm
Accessories 1Installation kit ES
Accessories 2Cover grille on operating side
AttachmentSpring return actuator 230 V AC


 Note:For further information relevant to design, in particular information on installation situations, please refer to the operating and installation manual.

Dimensions

  • DIMENSIONS

FKA2-EU with fusible link

Weight [kg] for casing length L = 305 [mm]/L = 500 [mm]

H [mm]B [mm]
200300400500600700800900100011001200130014001500
1004/55/66/87/98/119/1210/13
1504/65/77/98/109/1210/1311/15
2005/76/87/109/1210/1311/1512/1615/2016/2121/2723/2924/3126/3227/34
2507/98/1010/1211/1412/1614/1815/1916/2118/2324/2925/3127/3329/3530/38
3008/109/1211/1412/1513/1715/1916/2118/2319/2526/3228/3430/3632/3933/41
3508/1110/1311/1513/1715/1816/2018/2224/2926/3228/3430/3732/3934/4236/44
4009/1111/1312/1614/1816/2017/2219/2426/3128/3431/3733/3935/4237/4539/47
45010/1211/1413/1715/1917/2123/2826/3128/3430/3633/3935/4238/4540/4843/50
50010/1312/1514/1816/2018/2225/3027/3330/3633/3935/4236/4540/4843/5146/54
55015/1918/2221/2624/2826/3229/3532/3835/4137/4440/4743/5146/5449/57
60016/2019/2322/2725/3028/3331/3734/4037/4340/4743/5046/5349/5752/60
65017/2120/2523/2827/3230/3533/3936/4239/4642/4945/5348/5651/6055/63
70018/2221/2625/3028/3331/3735/4138/4441/4844/5248/5551/5954/6358/67
75019/2322/2726/3129/3533/3936/4340/4743/5047/5450/5854/6257/6661/70
80020/2424/2827/3331/3634/4038/4442/4945/5349/5753/6156/6560/6964/73

For more information on the constructions of the FKA2-EU, see functional description.

Accessories and Attachements

  • Accessories and ATTACHMENTS

Accessories 1 - Installation kits

Installation kit ES

L [mm]

Order code

500

ES

Installation kit WA

L [mm]

Order code

500

WA

Installation kit WE

L [mm]

Order code

500

WE



Accessories 2 – cover grille


Operating side

Installation side

Order code

Casing length [mm]

Cover grille-A0

305 / 500

-Cover grille0A

500

Cover grilleCover grilleAA*

500

Cover grilleflexible connectorAS

500

flexible connectorCover grilleSA

500

Cover grilleCircular spigotAR

500

Circular spigotCover grilleRA

500

Cover grilleProfile connecting frameAF

305 / 500

Profile connecting frameCover grilleFA

500


* When using the fire damper with cover grilles on both sides as an air transfer damper, the national specifications must be observed.

Accessories 2 – Flexible connectors

Operating side

Installation side

Order code

Casing length [mm]

flexible connector-S0

305 / 500

-flexible connector0S

500

flexible connectorflexible connectorSS

500

flexible connectorCover grilleSA

500

Cover grilleflexible connectorAS

500

flexible connectorCircular spigotSR

500

Circular spigotflexible connectorRS

500

flexible connectorProfile connecting frameSF

305 / 500

Profile connecting frameflexible connectorFS

500


Accessories 2 – Profile connecting frame

Operating side

Installation side

Order code

Casing length [mm]

Profile connecting frame-F0

305 / 500

-Profile connecting frame0F

305 / 500

Profile connecting frameProfile connecting frameFF

305 / 500

Profile connecting frameflexible connectorFS

500

flexible connectorProfile connecting frameSF

305 / 500

Profile connecting frameCover grilleFA

500

Cover grilleProfile connecting frameAF

305 / 500

Profile connecting frameCircular spigotFR

500

Circular spigotProfile connecting frameRF

305 / 500


Accessories 2 – Circular spigot

Operating side

Installation side

Order code

Casing length [mm]

Circular spigot-R0

305 / 500

-Circular spigot0R

500

Circular spigotCircular spigotRR

500

Circular spigotflexible connectorRS

500

flexible connectorCircular spigotSR

500

Circular spigotCover grilleRA

500

Cover grilleCircular spigotAR

500

Circular spigotProfile connecting frameRF

305 / 500

Profile connecting frameCircular spigotFR

500


Dimensions [mm]

Nominal size

B×H

øD

200

200 × 200

198

250

250 × 250

248

300

300 × 300

248

350

350 × 350

313

400

400 × 400

398

450

450 × 450

448

500

500 × 500

498

550

550 × 550

498

600

600 × 600

558

650

650 × 650

628

700

700 × 700

628

750

750 × 750

708

800

800 × 800

798



Accessories 2 – Extension pieces


Note:

The movement of the damper blade must not be obstructed by any accessory. The distance between the tip of the open damper blade and any accessory (moulded part, etc.) must be at least 50 mm.


Open blade protrusion [mm]


H

100

150

200

250

300

350

400

450

500

550

600

650

700

750

800

x

-204

-179

-154

-129

-104

-79

-54



-29 *




-4 *




21 *




46 *




71 *




96 *




121 *




146 *


y (1)



-8 *




17 *




42 *




67 *




92 *




117 *




142 *




167 **




192 **




217 **




242 **




267 **




292 **




317 **




342 **


y (2)

-204

-179

-154

-129

-104

-79

-54



-29 *




-4 *




21 *




46 *




71 *




96 *




121 *




146 *



* 1 *Extension piece required
** 2 Extension pieces required
(1) L = 305 mm
(2) L = 500 mm

Arrangement of extension pieces



L [mm]




H [mm]


Operating side

Installation side

305

100 – 400

195

305

405 – 800

195

2 × 195

500

100 – 400

500

405 – 800

195

195


Attachment – Limit switch

Attachment

Order code

Limit switch for damper blade position CLOSEDZ01
Limit switch for damper blade position OPENZ02
Limit switches for damper blade positions CLOSED and OPENZ03


Attachment – spring return actuator

Attachment

Order code

Spring return actuator 230 V (Belimo)Z43 
Spring return actuator 24 V (Belimo)Z45 
Spring return actuator 24 V (Belimo) including power supply unit BKN230-24-C-MP TRZ60 
Spring return actuator 24 V (Belimo) including power supply unit BKN230-24-C-MP TR and control module BKS24-1 TRZ61 
Spring return actuator 230 V (Siemens)Z43S
Spring return actuator 24 V (Siemens)Z45S

 
Attachment – Spring return actuator and RM-O-3-D

Attachment

Order code

With spring return actuator 230 V (Belimo) and integrated duct smoke detector type RM-O-3-DZ43RM
With spring return actuator 24 V (Belimo) and integrated duct smoke detector type RM-O-3-DZ45RM
With spring return actuator 230 V (Siemens) and integrated duct smoke detector type RM-O-3-DZ43RMS
With spring return actuator 24 V (Siemens) and integrated duct smoke detector type RM-O-3-DZ45RMS


Attachment – Spring return actuator and TROXNETCOM

Attachment

Order code

Spring return actuator 24 V and AS-EMZA07
Spring return actuator 24 V, RM-O-3-D and AS-EMZA12
Spring return actuator 24 V and MB-BAC-WA1/2ZB01
Spring return actuator 24 V and LON-WA1/B3ZL09
Spring return actuator 24 V and WA1/B3-ADZL10
Spring return actuator 24 V and WA1/B3-AD230ZL11
Spring return actuator 24 V and TNC-LinkboxZA14
Spring return actuator 24 V and MB-BAC-WA1/2ZB01

 
Attachment – Duct smoke detectors

Attachment

Order code

Duct smoke detector

RM-O-3-D

RM-O-VS-D


Duct smoke detectors are attachments and to be ordered separately.
RM-O-3-D can also be supplied assembled and wired for FKA2-EU with standard application.


Note:

For further information relevant to design, in particular information on installation situations, please refer to the operating and installation manual.

Karşıdan Yüklemeler

ürün bilgileri

broşürler

sertifikalar

işletme kılavuzları

Sayfayı paylaş

Bu sayfayı tavsiye et

E-posta ile bağlantı göndererek bu sayfayı tavsiye et

(*) ile işaretli alanlar zorunlu alanlardır.

Sayfayı paylaş

Tavsiyeniz için teşekkür ederiz!

Tavsiyeniz gönderilmiştir ve kısa sürede yerine ulaşacaktır.


İletişim

Sizin için buradayız

Lütfen mesajınızı ve istek türünüzü belirtiniz


(*) ile işaretli alanlar zorunlu alanlardır.

İletişim

Mesajınız için teşekkür ederiz!

Mesajınız gönderilmiştir ve kısa süre içinde işleme alınacaktır.
Servis-İstekler departmanımız en kısa sürede sizinle iletişim kuracaktır..


İletişim

Sizin için buradayız

Lütfen mesajınızı ve istek türünüzü belirtiniz


Attachment (max. 10MB)

(*) ile işaretli alanlar zorunlu alanlardır.

İletişim

Mesajınız için teşekkür ederiz!

Mesajınız gönderilmiştir ve kısa süre içinde işleme alınacaktır.
Servis-İstekler departmanımız en kısa sürede sizinle iletişim kuracaktır..